Thermal Management Of Outside Plant Telecommunication Cabinets: Design And CFD Modeling Methodology

ResearchCommons/Manakin Repository

Thermal Management Of Outside Plant Telecommunication Cabinets: Design And CFD Modeling Methodology

Show simple item record

dc.contributor.author Iqbal Mariam, Feroz Ahamed en_US
dc.date.accessioned 2010-07-19T19:54:48Z
dc.date.available 2010-07-19T19:54:48Z
dc.date.issued 2010-07-19
dc.date.submitted January 2010 en_US
dc.identifier.other DISS-10644 en_US
dc.identifier.uri http://hdl.handle.net/10106/4916
dc.description.abstract Over the years there has been a steady increase in the number of transistors being packed into the same footprint of a die, which has led to an increase in the power densities of electronics. The thermal management of electronic equipment therefore is becoming an integral part of packaging design. Access networks provide the last mile of connectivity for the telecommunication network users. In the access network, the outside plant telecommunication cabinets houses electronic components and switching devices. These cabinets are standalone outdoor cabinets and many a times they are located in hostile environments. Therefore, it is necessary that these cabinets provide environmental protection and thermal management for the electronics housed in it. The first part of the thesis deals with the design and thermal analysis of air-cooled high powered telecommunication cabinets. Commercial CFD code has been used to design and compare various cabinet configurations. This has enabled in reducing the unnecessary construction of cabinet prototypes and elaborate experimental tests, resulting in cost savings and reduction in lead time. The electronics in these cabinets are powered by DC current and have backup batteries to support them in the event of a power failure. The life of a battery is dependent on the nature of the load applied, recharging conditions and most importantly ambient temperatures. Based on the location and time of day, the ambient temperature can be anywhere between -40°C to 50°C. But for long standing battery life, the temperature inside the battery compartment should be maintained at 25°C. Active cooling using air-conditioners are often used to achieve this, but air-conditioners are difficult to backup and are high in maintenance. A more convenient way to cool the battery compartments are to use Thermo-electric Coolers (TEC), as they are compact and quite in operation. The second part of the thesis explains a modeling methodology to develop a TEC air-to-air heat exchanger that is used in the thermal management of the battery compartments. The numerical results thus obtained are validated with experimental results, and the validated model is further used to try out various test scenarios for the telecommunication cabinet. en_US
dc.description.sponsorship Agonafer, Dereje en_US
dc.language.iso EN en_US
dc.publisher Mechanical Engineering en_US
dc.title Thermal Management Of Outside Plant Telecommunication Cabinets: Design And CFD Modeling Methodology en_US
dc.type M.S. en_US
dc.contributor.committeeChair Agonafer, Dereje en_US
dc.degree.department Mechanical Engineering en_US
dc.degree.discipline Mechanical Engineering en_US
dc.degree.grantor University of Texas at Arlington en_US
dc.degree.level masters en_US
dc.degree.name M.S. en_US
dc.identifier.externalLink https://www.uta.edu/ra/real/editprofile.php?onlyview=1&pid=4
dc.identifier.externalLinkDescription Link to Research Profiles